Instruction manual ME3816-6B

Parameter No.6: Current Control Setting at Stop

No.
Category
Name
Unit
Input range
Default setting
at shipping
6
A
Current control
setting at stop
-
Disabled : Powerful stop
Enabled : Energy-saving stop
Disabled
  • The control method for ELECYLINDER stop can be selected.
  • If "Disabled", a constant current value will be transmitted to the motor, stopping it.
    This limits fine vibration when stopping, bringing the unit to a complete stop.
  • If "Enabled", a current appropriate to the load will be transmitted to the motor, stopping it.
    This limits the amount of power consumed while stopping.
  • If abnormal noise or vibration occurs during a gradual stop, setting to "Enabled" may fix the issue. Moreover, setting to "Enabled" can also fix issues in which the command position cannot quite be attained.

Caution

  • If "Disabled", even if a pulse deviation within ±2 from the target position remains, movement towards the target position will not continue.
  • If "Enabled", if a pulse deviation of ±1 or more from the target position remains, movement towards the target position will continue.