Alarm Group B: Motor Abnormality Alarm

Motor abnormality occurred.
No.
Cause
Countermeasure
The internal temperature of the motor may be too high.
Improve the surrounding environment of the motor so that the ambient temperature is 40°C or less.
If the abnormality is resolved upon turning the power back on after the ambient temperature is lowered, the internal temperature may have been excessive.
[Countermeasure examples]
Remove the heat source/turn OFF the heat source/install a fan/install a temperature shield/improve thermal conductivity of the base/install a heat dissipation fin, etc.
The ELECYLINDER may be being used under conditions exceeding the specifications.
Check the specification values such as payload, acceleration/deceleration and speed, and adjust them appropriately.
If this alarm recurs after performing the inspection above and improving the power supply environment, it is highly likely that the motor has failed.
Replace the motor unit.
For details, refer to the Instruction manual for each ELECYLINDER, Maintenance and Inspection.