Alarm Group C: Controller Abnormality Alarm
Controller abnormality occurred.
No. | Cause | Countermeasure |
|---|---|---|
1 | The controller is affected by the noise of a peripheral device and cannot operate normally. | Shut down the power supply of the peripheral device and operate only with the ELECYLINDER, then check to see whether this alarm persists. If it does not, there is a possibility that the ELECYLINDER is affected by the noise from the peripheral device. Reconsider the noise countermeasures (grounding, power line wiring, electrostatic shielding, etc.) for the peripheral device. |
2 | If this alarm recurs after performing the inspection above and improving the power supply environment, it is highly likely that the controller has failed. | Replace the motor unit. For details, refer to the Instruction manual for each ELECYLINDER, Maintenance and Inspection. |